BWL INDUSTRIAL CABLE GLAND

Description

BWL type Industrial Cable Gland for Indoor use with all types of Steel Wire Armour (SWA) & Aluminium Wire Armour (AWA) cable, providing Mechanical retention & Electrical continuity via armour wire termination.

Technical Data
TypeBWL (Industrial)
Design SpecificationBS 6121: Part 1:1989, IEC 62444: 2010 & EN 62444 : 2013
Mechanical Classification* *Retention = Class D, Impact = Level 8
Electrical Classification**Category B
Enclosure ProtectionIK10 to IEC 62262 (20 Joule) Brass
CertificateWIP
Operating Temperature-60°C to +200°C
Ingress Protection RatingIP 2X
Standard Gland MaterialBrass (BS EN 12164/ Grade CuZn39Pb3)
Standard ThreadISO Metric
Cable TypeSteel Wire Armour (SWA) & Aluminium Wire Armour (AWA)
Armour ClampingDetachable Armour Cone & Clamping Ring
Optional Gland MaterialsBrass Nickel Plated, Aluminium
Optional AccessoriesAdaptor, Reducer, Earth Tag, Lock Nut, Serrated Washer, Shroud
Gland Kits Available1 Cable Gland, 1 Lock Nut, 1 Earth Tag, 1 PVC Shroud

**Mechanical & Electrical Classification applied as per IEC/EN 62444

BWL Industrial Cable Gland Selection Table

Gland Dimensions

Cable Dimensions

Cable Gland SizeEntry Thread EMinimum Thread LengthMaximum LengthAcross FlatsAcross CornersCable Bedding DiameterOverall Cable DiameterArmour Range
StandardL1LAFACBA
MetricMetricMaxMaxMaxMaxMaxMinMax
20S/16M2012.0022.0024.0026.409.0014.000.801.25
20SM2012.0022.0024.0026.4012.0016.000.801.25
20M2012.0028.0030.5033.5014.0021.000.801.25
25M2512.0032.0037.5041.2020.0026.401.251.60
32M3212.0034.0046.0050.6026.2034.001.602.00
40M4015.0036.0055.0060.5032.2040.501.602.50
50SM5015.0036.0060.0066.0038.0046.802.002.50
50M5015.0038.0070.0077.0044.0053.202.002.50
63SM6315.0044.0075.0082.5050.0059.502.002.50
63M6315.0044.0080.0088.0056.0066.002.002.50
75SM7515.0050.0089.0098.0062.2072.202.002.50
75M7515.0050.0099.00109.0068.5078.602.503.15
90M9017.0056.00108.00119.0080.0090.503.154.00