Ex db

EX E1FU CABLE GLAND

Description

Ex E1FU type Hazardous Area Cable Gland Certified in Flamproof (Type ‘db’), Increased Safety (Type ‘eb’) & Dust Ignition Protection (Type ‘ta’) for Indoor & Outdoor use in Zone 1, 2, 20, 21 & 22 hazardous areas with all types of armoured cable, providing an Environmental Seal on cable Inner Bedding & Outer Sheath, also providing Mechanical Cable Retention & an Electrical Continuity via armour wire termination.

Technical Data
TypeEx E1FU
Design SpecificationBS 6121: Part 1:1989, IEC 62444 : 2010 & EN 62444 : 2013
Mechanical Classification**Retention = Class D, Impact = Level 8
Electrical Classification**Category B
Enclosure ProtectionIK10 to IEC 62262 (20 Joule) Brass & Stainless Steel Only
Operating Temprature-40°C to + 85°C
Ingress Protection RatingIP 66 / IP 68***
Standard Gland MaterialBrass (BS EN 12164 / Grade CuZn39Pb3)
Seal MaterialThermoset Elastomer
Standard ThreadISO Metric / NPT
Cable TypeWire Braid Armour, Strip Armour, Piliable Wire Armour, Steel Tape Armour, Single Wire Armour , Aluminium Wire Armour
Armour ClampingDetachable Armour Cone & Universal Armour Clamping Ring
Sealing TechniqueInner Displacement Seal & Load Retention Outer Seal
Sealing AreaCable Inner Bedding & Outer Sheath
Optional Gland MaterialBrass Nickel Plated, Brass Electroless Nickel Plated, Stainless Steel(SS316 & SS316L)
Optional AccessoriesAdaptor, Reducer, Earth Tag, Lock Nut, Entry Thread Nylon & Fiber Washer, Serrated Washer, Shroud
Global Certification
Compliance StandardsEN / IEC 60079-0, 1, 7, 31
ATEX CertificateDNV 22ATEX73142X
Code of ProtectionCabex Electrical Components | EX E1FU CABLE GLAND | M2 Cabex Electrical Components | EX E1FU CABLE GLAND || 2G 1D Cabex Electrical Components | EX E1FU CABLE GLAND 2460, IP 66 / IP 68
IECEx CertificateIECEx DNV 22.0002X
Code of ProtectionEx db | Mb Ex eb | Mb, Ex db || C Gb Ex eb || C Gb, Ex ta ||| C Da
EAC CertificateApplied for Certificate
DNV GL CertificateApplied for Certificate
ABS CertificateApplied for Certificate
PESO CertificateA/P/HQ/GJ/104/6052 (P568100)

**Mechanical & Electrical Classification applied as per IEC / EN 62444

***IP 68 : Tested at 30m depth for 7 days (Alternate depth & duration can be provided upon request)

Ex E1FU Cable Gland Selection Table

Gland Dimensions

Cable Dimensions


Cable
Gland
Size
Entry Thread
E
Minimum
Thread
Length
Maximum
Length
Across
Flats
Across
Corners
Cable
Bedding
Diameter
Overall
Cable
Diameter
Armour
Range
StandardOptionL1LAFACBADirection 1Direction 2
MetricNPT*NPT*MetricNPTMaxMaxMaxMinMaxMinMaxMinMaxMinMax
20S/16M201/2″3/4″15.0020.0073.5024.0026.503.108.706.1011.600.801.250.101.00
20SM201/2″3/4″15.0020.0073.5024.0026.507.0011.709.5016.000.801.250.101.00
20M201/2″3/4″15.0020.0076.0031.0034.0010.0014.0012.5021.200.801.250.101.00
25SM253/4″1″15.0020.5088.5037.5041.2511.0016.0014.1022.001.251.600.101.00
25M253/4″1″15.0020.5091.5037.5041.2514.5020.0018.5026.301.251.600.101.00
32M321″1-1/4″15.0025.5095.5046.0050.5018.5026.4024.0034.001.602.000.101.00
40M401-1/4″1-1/2″15.0026.0096.5055.0060.5025.0032.3028.0040.601.602.000.101.00
50SM501-1/2″2″15.0026.50101.0060.0066.0031.5038.5035.5046.702.002.500.101.00
50M502″2-1/2″15.0027.00105.5070.0077.0036.5044.0040.8053.202.002.500.101.00
63SM632″2-1/2″15.0027.00103.0075.0082.5042.5050.0045.7059.402.002.500.101.00
63M632-1/2″3″15.0040.00107.0081.0089.0048.5056.2054.8066.102.002.500.101.00
75SM752-1/2″3″15.0040.00114.5091.00100.0055.0062.0059.5072.202.002.500.101.00
75M753″3-1/2″15.0042.00126.00100.00110.0061.5068.0067.0079.502.503.150.101.00
90M903-1/2″4″20.0043.00144.50114.00125.2565.0080.0075.0090.502.753.500.101.00